Skip to main content
Follow us on: 
Plate & Gaskets | Data Sheets

Tranter GX-265P.

Tranter GX-265P

DATA SHEET

Tranter GX-265P

Plate heat exchanger

The Plate Heat Exchanger has 4 connections as standard and should be installed with min. 1500 mm space on both sides for service work.
Subject to alterations without prior notice

Technical Data

Dimensions, mm
Standard connection dimension    DN300
Tightening bolt                                     M39
No. of long tightening bolts (TL)       4
No. of short tightening bolts (TS)     24 
Cover thickness                                   90 mm
Weight of guiding bar                        43 kg/m
Weight of tightening bolt                   8,1 kg/m
A-dimension                                         3,9*n mm
C-dimension                                         LG+190 mm
F-dimension                                          LG+10 mm
Weight plate+gasket (W)
      AISI 304/316 0,6 mm                       14,0 kg
     Titanium 0,6 mm                              8,4 kg
Weight Frame                                        5640+n*W kg

Max No of plates   LTL    LG     C      F
            35                500  1300 1490 1310
            76                750   1300 1490 1310
            105               1050 1300 1490 1310
            126               1050 1600 1790 1610
            155               1350 1600 1790 1610
            176                1350 1950 2140 1960
            213               1650 1950 2140 1960
            226              1650 2200 2390 2210
            255              1950 2200 2390 2210
            276              1950 2500 2690 2510
            305              2250 2500 2690 2510
            326              2250 3000 3190 3010
            388              3000 3000 3190 3010
            450              3000 3500 3690 3510

LTL = Length of long tightening bolt, based on 6 x n + 290 mm
LG = Length of guiding bar, based on 6 x n + 870 mm
n = number of plates

Total max no. of plates
AISI 304/316 0,6 mm      450

 

All data is based on plates with material AISI 304/316 and thickness 0,6 mm.

Ontario service representative for Armstrong Plate & Frame and Shell & Tube Exchangers.

Ontario service representative for Caron et files Custom Industrial Heat Exchangers, Heater Coils, Steam Unit Heaters

Ontario service representative for Bray Butterfly Valves, Bray Ball Valves, Bray Check Valves, Bray Knife Gate Valves, Bray Actuators – Electric, Manual & Pneumatic Solenoids

Ontario service representative for Puroflux line of Permanent Media Filters, Centrifugal Separators and Disc Filters.

Ontario service representative for Filter Solutions Inc. line of Magnetic Separators, Bag and Cartridge Housings and Wedge Wire Filters & Strainers.

Ontario service representative for REOTEMP Instruments line of Pressure Gauges, Bi-Metal Thermometers and RTDs

Ontario service representative for Clearstream Filters line of Self-Cleaning Indexing Media Filters and Custom Filter Bags

Ontario service representative for Xylem, Bell & Gossett Plate & Frame and Shell & Tube Exchangers. Ontario Service representative for TTP (API Heat Transfer Company) Oil Coolers.

Ontario Service representative for SWEP (A Dover Company) Brazed Plate Heat Exchangers.

Ontario Service representative for Kelvion Brazed Heat Exchangers, Plate & Frame Heat Exchangers, and Shell & Tube Heat Heat Exchangers.

WHEN SHOULD A PLATE & FRAME HEAT EXCHANGER BE SERVICED?

As a heat exchanger becomes fouled with dirt, debris or scale, often the modulating valve provides additional hot or cold liquid to help compensate for the loss of efficiency of the heat exchanger.

Over time the control valve will continue to open fully. Unfortunately, on the hottest or coldest days, even with the valve fully open the heat exchanger cannot meet the thermal transfer requirements and the situation becomes critical.

Monitoring just the operating temperature provides a false sense of security. Recording the difference in the outlet and inlet pressures provides a more accurate result of the amount of fouling.

Fouling equal to the thickness of a piece of paper represents a 20% loss of thermal efficiency. In addition, the energy cost for pumps increases since the pump must work harder to overcome the increased pressure resistance through the PHE

T.H. Industrial Solutions Inc. (THS) has been servicing industrial plate and frame heat exchangers as with shell and tube heat exchangers.  Professionally solving process problems across Canada since 2009. THS head office is located in Pickering, Ontario with a 6,000 square foot service center in Hamilton, Ontario.

Today there are fewer qualified people in this industry that know the products and understand the applications. Utilizing hands on experience and knowledge that has been gained by our THS sales and service technicians for over the past 30 years, we will take the time to understand what you require and strive to provide a prompt, educated and accurate response at a competitive price.

Our Heat Exchanger Cleaning Services, along with heat exchanger gasket replacement systems, and knowledge of heat exchanger gasket materials make THS your Industrial Heat Exchanger Service Solution

THS Logo
HEAD OFFICE

1550 Bayly Street, Unit 15
Pickering, ON L1W 3W1

T 905 831-4963

SERVICE CENTER

76 Harlowe Road, Unit 5, 6 & 7
Hamilton, ON L8W 3R6

T 905 318-0777
F 905-318-8422

Contact THS SERVICE


Proudly Canadian logo

©2024 T. H. Industrial Solutions Inc.  SITEMAP