Alfa Laval TL15.

Alfa Laval TL15

DATA SHEET

Alfa Laval TL15

Plate heat exchanger

General heating and cooling duties.

Typical capacities

Liquid flow rate
Up to 120 kg/s (1900 gpm), depending on media, permitted pressure drop and temperature program.

Plate types
TL15-B

Frame types
FM, FG, FD and FS

Standard Materials

Frame plate
Mild steel, Epoxy painted

Nozzles
Carbon steel
Metal-Lined: Stainless steel, Titanium, nickel
Rubber lined: Nitrile, EPDM

Plates
Stainless steel: Alloy 304, Alloy 316
Titanium
Nickel

Gaskets
NBRB, NBRP, EPDMP, EPDMAL

Technical Data

Pressure vessel codes PED, ASME, pvcALS™
Mechanical design pressure (g) / temperature

FM     pvcALS™                     1.03 MPa / 180°C  (150 psi / 356ºF)
FG     pvcALS™                     2.0 MPa / 50°C
FG     PED                              2.0 MPa / 50°C 
FG     ASME                           150 psig / 482°F
FD     ASME                           300 psi / 482°F
FS      pvcALS™                     3.5 MPa / 50°C
FS      PED                              3.5 MPa / 50°C
FS      ASME                           460 psi / 482°F

Connections

FM    pvcALS™       Size 150 mm       DIN/GB/GOST PN10, ASME CI. 150, JIS 10K
FG    pvcALS™       Size 150 mm       DIN/GB/GOST PN16, PN25, ASME Cl. 150, JIS 10K, JIS 16K
FG    PED                 Size 150 mm       DIN PN16, PN25 ASME Cl. 150
FG    ASME              Size 6”                  ASME Cl. 150
FD     ASME             Size 6”                  ASME Cl. 300
FS      pvcALS™       Size 150 mm      DIN/GB/GOST PN25, PN40/ASME Cl.300/ JIS 20K
FS      PED                Size 150 mm       DIN PN25, PN40 ASME Cl. 300
FS      ASME             Size 6”                  ASME Cl. 300

Maximum heat transfer surface
990 (1,1 x 900) m2 (10660 sq.ft)

Measurements mm (inch)
Type                                               H                          W                              h
TL15-FM/pvcALS™           2752 (108 1/3")        610 (24")               342 (13 1/2")
TL15-FG/PED/pvcALS™   2752 (108 1/3")        637 (25")              342 (13 1/2")
TL15-FG/ASME                  2752 (108 1/3")        646 (25 3/7")       342 (13 1/2")
TL15-FD/ASME                  2752 (108 1/3")        646 (25 3/7")       342 (10 1/3")
TL15-FS/PED/pvcALS™    2752 (108 1/3")        646 (25 3/7")       342 (13 1/2")
TL15-FS/ASME                   2752 (108 1/3")        646 (25 3/7")       342 (13 1/2")

Ontario service representative for Armstrong Plate & Frame and Shell & Tube Exchangers.

Ontario service representative for Caron et files Custom Industrial Heat Exchangers, Heater Coils, Steam Unit Heaters

Ontario service representative for Bray Butterfly Valves, Bray Ball Valves, Bray Check Valves, Bray Knife Gate Valves, Bray Actuators – Electric, Manual & Pneumatic Solenoids

Ontario service representative for Puroflux line of Permanent Media Filters, Centrifugal Separators and Disc Filters.

Ontario service representative for Filter Solutions Inc. line of Magnetic Separators, Bag and Cartridge Housings and Wedge Wire Filters & Strainers.

Ontario service representative for REOTEMP Instruments line of Pressure Gauges, Bi-Metal Thermometers and RTDs

Ontario service representative for Clearstream Filters line of Self-Cleaning Indexing Media Filters and Custom Filter Bags

Ontario service representative for Xylem, Bell & Gossett Plate & Frame and Shell & Tube Exchangers. Ontario Service representative for TTP (API Heat Transfer Company) Oil Coolers.

Ontario Service representative for SWEP (A Dover Company) Brazed Plate Heat Exchangers.

Ontario Service representative for Kelvion Brazed Heat Exchangers, Plate & Frame Heat Exchangers, and Shell & Tube Heat Heat Exchangers.

WHEN SHOULD A PLATE & FRAME HEAT EXCHANGER BE SERVICED?

As a heat exchanger becomes fouled with dirt, debris or scale, often the modulating valve provides additional hot or cold liquid to help compensate for the loss of efficiency of the heat exchanger.

Over time the control valve will continue to open fully. Unfortunately, on the hottest or coldest days, even with the valve fully open the heat exchanger cannot meet the thermal transfer requirements and the situation becomes critical.

Monitoring just the operating temperature provides a false sense of security. Recording the difference in the outlet and inlet pressures provides a more accurate result of the amount of fouling.

Fouling equal to the thickness of a piece of paper represents a 20% loss of thermal efficiency. In addition, the energy cost for pumps increases since the pump must work harder to overcome the increased pressure resistance through the PHE

T.H. Industrial Solutions Inc. (THS) has been servicing industrial plate and frame heat exchangers as with shell and tube heat exchangers.  Professionally solving process problems across Canada since 2009. THS head office is located in Pickering, Ontario with a 6,000 square foot service center in Hamilton, Ontario.

Today there are fewer qualified people in this industry that know the products and understand the applications. Utilizing hands on experience and knowledge that has been gained by our THS sales and service technicians for over the past 30 years, we will take the time to understand what you require and strive to provide a prompt, educated and accurate response at a competitive price.

Our Heat Exchanger Cleaning Services, along with heat exchanger gasket replacement systems, and knowledge of heat exchanger gasket materials make THS your Industrial Heat Exchanger Service Solution

THS Logo
HEAD OFFICE

1550 Bayly Street, Unit 15
Pickering, ON L1W 3W1

T 905 831-4963

SERVICE CENTER

76 Harlowe Road, Unit 5, 6 & 7
Hamilton, ON L8W 3R6

T 905 318-0777
F 905-318-8422

Contact THS SERVICE


Proudly Canadian logo

©2024 T. H. Industrial Solutions Inc.  SITEMAP